MGE Galaxy 3500 15kVA 400V, Start-Up 5X8
Part# G35T15KHS
EAN:
MGE Galaxy 3500 - UPS - AC 380/400/415 V - 12 kW - 15000 VA - 3-phase - no battery - Ethernet 10/100, RS-232 - output connectors: 3
Native product specifications. The product description originates from Cnet. Foxway Distribution accepts no responsibility for error or misinformation in product descriptions from Cnet.
Product specifications
Product Description | MGE Galaxy 3500 - UPS - 12 kW - 15000 VA |
Manufacturer Warranty | 1-year warranty |
Dimensions (WxDxH) | 52.3 cm x 83.8 cm x 149 cm |
Weight | 258 kg |
Networking | Ethernet 10/100, RS-232 |
Device Type | UPS - external |
Battery | No battery |
Remote Management Protocol | SNMP 1, Telnet, SNMP 3, HTTP, HTTPS |
Input Voltage | AC 380/400/415 V |
Output Voltage | AC 380/400/415 V ± 5% |
Included Accessories | Bolt down brackets |
Input Wiring | 3-phase |
Power Capacity | 12 kW / 15000 VA |
Input Connectors | 1 x hardwire 5-wire (3PH + N + G) |
Output connectors | 1 x hardwire 4-wire (3PH + G) ¦ 1 x hardwire 5-wire (3PH + N + G) ¦ 1 x Terminal Block (Screw) |
General features
Device Type | UPS - external |
Ports
Interfaces | 1 x management (Ethernet) - RJ-45 ¦ 1 x management (RS-232) |
Expansion Slots | 1 (total) / 0 (free) x SmartSlot |
Warranty
Service & Support | Limited warranty - 1 year ¦ Installation - availability: 8 hours a day / Monday-Friday ¦ Configuration - availability: 8 hours a day / Monday-Friday |
Network
Remote Management Interface | Ethernet 10/100, RS-232 |
Remote Management Protocol | SNMP 1, Telnet, SNMP 3, HTTP, HTTPS |
Compliance
Included Accessories | Bolt down brackets |
Cables Included | Serial cable - external |
Features | Audible alarm, LCD display, built-in maintenance bypass, built-in static bypass |
Compliant Standards | ISO 9001, IEC 61000-3-2, IEC 61000-3-3, ISO 14001, EN 50091-2, IEC 62040-3, IEC 62040-1-1 |
HDD / SSD tolerance
Min Operating Temperature | 0 °C |
Max Operating Temperature | 40 °C |
Humidity Range Operating | 0 - 95% |
Sound Emission | 51.3 dBA |
Battery
Type | No battery |
Capacity
UPS Technology | On-line |
Input Voltage | AC 380/400/415 V |
Input Voltage Range | AC 304 - 477 V |
Input Voltage Range (Adjustable) | AC 340 - 460 V |
Frequency Provided | 47 - 53 Hz |
Input Wiring | 3-phase |
Frequency Required | 40 - 70 Hz |
Input Connectors | 1 x hardwire 5-wire (3PH + N + G) |
Power Output Connectors Details | 1 x hardwire 4-wire (3PH + G) ¦ 1 x hardwire 5-wire (3PH + N + G) ¦ 1 x Terminal Block (Screw) |
Output Voltage | AC 380/400/415 V ± 5% - 47 - 53 Hz |
Power Capacity | 12 kW / 15000 VA |
Output Waveform | Sinewave |
Surge Suppression | Yes |
Circuit Protection | Circuit breaker |
Physical dimensions
Width | 52.3 cm |
Depth | 83.8 cm |
Height | 149 cm |
Weight | 258 kg |
Shipping dimensions
Shipping Width | 65 cm |
Shipping Depth | 106 cm |
Shipping Height | 164 cm |
Shipping Weight | 290 kg |
Specifications
UPS is supplied without batteries. To be used with either external third party battery system, or with internal long life modular batteries (SYBTH4).
- Dual mains input
It increases availability by allowing the UPS to be connected to two separate power sources. - Hot-swappable batteries
It ensures clean, uninterrupted power to protected equipment while batteries are being replaced - Parallel-capacity capable
Increases total power capacity by using multiple UPSs simultaneously. - Advanced electrical features
Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high efficiency! - Frequency and voltage regulation
It gives higher application availability by correcting poor frequency and voltage conditions without using the battery. - Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS overload condition or fault. - Generator compatible
It ensures clean, uninterrupted power to protected equipment when generator power is used. - Front-access servicing
It simplifies installation and maintenance while minimizing space requirements. - Built-in Web/SNMP management
Full-featured management via a Web browser as well as comprehensive management from a network management system! - Environmental monitoring
Prevent equipment failure from a full range of threatening environmental conditions. - LCD graphics display
Text and mimic diagrams display modes of operation, system parameters and alarms. - Audible alarms
Provides notification of changing utility power and UPS conditions. - Input power factor correction
It minimizes installation costs by enabling the use of smaller generators and cabling. - Excellent footprint
Small UPS footprint provides maximum usage of valuable electrical room floorspace. - Temperature-compensated battery charging
It prolongs battery life by regulating the charge voltage according to battery temperature.